SECTION 7 Planning and Pre-wiring
Information
ZONE
CONTROL FOR HOME AND OFFICES - GREATER COMFORT GREATER ENERGY SAVINGS.
With an
Airzone system directing the flow of air exactly where and when you need it,
energy is not wasted over-heating or cooling an area that is already
satisfied or unoccupied. Fuel savings of 10 to 30 percent or more are
possible, depending on how the Airzone System is used or "managed."
DIFFERENT TYPES OF
ZONE CONTROL
Three
different types of zone control with Airzone give you three different levels
of capabilities.
Primary
Zones- (Airzone Systems with control panels) A primary zone is a zone with a
thermostat that not only controls Flexdampers but also controls the
operation of the HVAC System, and is totally automatic. When a primary zone
thermostat calls for air, the Flexdampers serving this zone will open,
Flexdampers serving other zones will close, and the HVAC system will
operate.
Slave
Zones- (SPP panels with no Control Panels) Slave zones are used to simply
open and close certain ducts, such as those serving an unused guest
bedroom. While slave zones can be controlled by a toggle switch or
thermostat, only the Flexdamper(s) are controlled: The HVAC unit is not
brought on or off. Airzone’s SPP Panel, on its own, is an example of a
slave zone.
Combination Primary/Slave Zones: Suppose you wanted to zone a home into
three primary zones with a SPP and control panel, and also wanted to control
a seldom used utility and guest bedroom. Use a SPP-3/control panel combo
tied with an SPP-2 for this control. Order the SPP-2 without a pump.
Why not
use an expanded SPP-3/control panel combo for five primary zones of
control? Besides greater cost, if the utility room were set up as a primary
zone, it could be the only zone calling for air - forcing you to use some
type of static pressure relief system. On the other hand, if this area were
a small office where temperature was critical, a primary zone would be the
way to go.
DESIGNING ZONE
CONTROL INTO A HOME OR OFFICE - NEW CONSTRUCTION OR RETROFIT.
ALL
SYSTEMS - Designing a zoning system into a home or office is easy, if a few
basics are understood. The zoning system should always allow a certain
amount of airflow over the coil or heat exchanger of the HVAC system, so the
Airzone system should never be installed in such a way as to restrict a
significant amount of the total airflow going through the HVAC
furnace/evaporator coil.
As an
Airzone System begins to close dampers, the air velocity and static pressure
will increase, and more air will be moved through the remaining open ducts.
This occurs up to the point that the HVAC fan capacity is exceeded and the
amount of airflow is reduced. At that point, simply use one of several
static pressure
control systems or methods offered by Retrozone, Inc.
Where to
mount the Airzone Panel: The Airzone Panel(s) can be mounted by the HVAC
unit, or remotely if desired, as long as the panel(s) are easily
accessible. Avoid bedroom closets or locations where the minor noise of the
Airzone Panel could be a problem.
Where to
mount thermostats: Thermostat placement is critical to maximize the benefits
of zoning. Thermostats should be placed at a central location in each zone,
on an interior wall. Avoid placement where lamps, sunlight, or other
artificial heat loads can affect the thermostat.
NEW CONSTRUCTION
The
Airzone System can often eliminate the need for two or more separate HVAC
systems, while at the same time offering more zones of control. Because the
Airzone System manages airflow so efficiently, you can use a smaller HVAC
system with no loss of comfort and big gains in energy savings. In fact, the
Airzone System works best with a properly sized or slightly undersized unit.
On
installations where the duct system is being designed to use zoning, the
size of the ducts can be slightly increased to enhance the zoning
performance. When designing the duct system for zoning, caution should be
used to avoid two extremes: First, over sizing the ducts to a point that,
when all Flexdampers are open, air velocity (how fast the air is moving
through the duct) falls to a point that air is not properly circulated in
the duct. Second, under sizing the ducts to a point where too much airflow
is restricted when only one zone is calling for air.
For an
Airzone System of three zones or less, each zone's duct(s) should be sized
to handle 60 to 70 percent of the total airflow. This will enable an
installer to avoid using any kind of static pressure relief system, since
both extremes mentioned above will be avoided. Instead, static pressure and
air velocity will vary as zone dampers open and close. Call a Retrozone
expert for more information.
New
Construction - Designing the duct system layout.
Designing
a duct system to include an Airzone System can be easier than designing a
single zone duct system. Why? A conventional single zone system must have
the duct sizes carefully calculated to the load on each room or zone. Even
so, this method of duct sizing cannot compensate for sun load and other
changing variables.
An
Airzone System automatically controls the airflow to each zone, making the
size of the duct serving the area less critical. The ducts should be sized
larger than ducts in a single zone system so that each zone can receive
enough air to quickly satisfy.
Two and
three (and sometime four) zone systems using the Airzone System can be
designed with no static pressure control systems. Airzone Systems using
more zones will typically need one of the static pressure control systems.
Planning
the layout of the duct system in new construction requires not only
attention to the floor plan of the home, but also how the homeowner will be
using the home. Making each room a zone can be impractical because of the
expense; instead the home should be divided into areas or zones that are
used typically at the same time. An easy example is a home that has all the
living areas on one end, and the sleeping areas on the other. The designer
might make this a two zone application - living and sleeping.
The duct
system should be designed so that the ducts serving each zone are accessible
for easy Flexdamper installation.
Checklist for
installing an Airzone System in new construction:
A.
Design duct system so that each duct is accessible for Flexdamper
installation and service. All ducts from each zone should connect together
and then home run back to the plenum, so that each zone has only one or two
ducts, thus needing only one or two Flexdampers. Where the capacity of a 12
inch or larger duct is needed for a given zone, consider using two smaller
Flexdampers/ducts per zone, since response time will be faster.
B.
Up-size the ducts according to the guidelines in this section and the Manual
J guidelines. It is very important to have plenty of duct capacity into
each zone so that zone may satisfy quickly, should it be the only zone
calling. Don't worry about a zone getting to much air; the Airzone system
will automatically control that.
C. Run
all thermostat wire during the construction phase. Run 8 conductor, 22 gauge
thermostat wire, or call for specific details for your system. Be sure to
locate thermostats central to each zone.
D.
Depending on the duct layout and the mounting location of the Airzone System
Panel, run tubing during construction.
E. Do not
oversize the HVAC system - bigger is not better with zoning. Consult Manual
J for details.
RETROFIT-DESIGNING
RETROZONE INTO AN EXISTING HOME OR OFFICE.
The
Airzone System was especially designed for existing applications where the
ducts are already in place, since Flexdampers can be installed easily in
existing ducts. The Airzone System can correct many existing system
problems. See "Correcting Problems in Existing Systems" for details.
Try to
divide the home into two or more general zones of use. Also inspect the
duct layout to determine how the home can be divided. Several ducts can be
tied together to create one zone.
Attempt
to limit the number of primary zones to six or less.
Each zone
will need a thermostat centrally located within that zone.
Experience has shown that most duct systems can be divided into two equal
zones (and sometimes three) and need no static pressure relief system.
REGULATING THE
STATIC PRESSURE ON YOUR SYSTEM
As
mentioned earlier, some care must be taken to insure that an adequate amount
of airflow continues to pass through the HVAC system to insure proper
operation.
While
restricting too much airflow can cause several HVAC problems, these problems
are easy to deal with or solve using various Retrozone products and design
techniques.
Problems
with restricting too much airflow are rare for the following reasons: When
only one zone is calling (the most restrictive mode) that thermostat is
satisfied very quickly, before problems such as coil icing can occur.
With
Airzone Systems, many options and safeties exist to control these potential
concerns. Install the Airzone System according to the instructions. Should
you have a problem, use one of the solutions below for correction.
A. ECL
switch - Two and three zone new construction / retrofit applications
typically need nothing more than Airzone's inexpensive ECL switch installed
on the suction line of the evaporator coil to monitor against coil freeze
up.
If
refrigerant temperature drops too low, all Flexdampers will open. The ECL
switch is recommended for all systems except heat pumps. Heat Pumps should
use a control panel that accepts duct sensors for hi/lo protection.
B. Dump
Zones - If too much airflow restriction is suspected, simply remove a
Flexdamper from a duct serving a common area like a hallway where
temperature control is not critical. This "wild duct" is open all the time,
and relieves system pressure.
C.
Barometric relief damper - This Retrozone product is installed in a duct
between your supply air plenum and return air plenum, and opens
automatically to relieve pressure as zones close off.
D. Static
Pressure Control System - Similar to the barometric damper, the Static
Pressure Control System provides static pressure control for commercial
installations over 5 tons, and is available in all duct sizes.
E.
Controlled Damper Leakage - Round and Rectangular Flexdampers can be
installed to leak 10% or more to reduce system pressure.
SIZING THE HVAC
UNIT CORRECTLY
Fact 1:
The most efficient HVAC unit is one that is sized correctly to the load on a
home or office.
Fact 2:
Many HVAC units are oversized for the home or office.
Over-sizing your HVAC system may sound like a great idea - plenty of
capacity to keep you warm or cool. But the truth is that an oversized unit
actually decreases your comfort AND wastes energy at the same time. An
Airzone System, by eliminating over cooled and over heated areas, stretches
the capacity of the unit. Further, when unused zones are shut down, even a
severely undersized HVAC unit (not recommended) has the ability to provide
total comfort in the zones that are being used.
Almost
everyone has some type of a problem with comfort in their home, as well as a
desire to save energy. Airzone Sysems can be used to correct many types of
comfort and/or energy problems:
A.
Undersized HVAC System - Review the '"Sizing the HVAC Unit Correctly"
Section above to understand why Airzone Sysems can turn the undersized unit
into a highly efficient and comfortable unit.
Without
zoning, most HVAC systems have to be sized for "design conditions," meaning
the hottest and coldest days of the year. However, these peak temperature
extremes account for only about 5% of the year. The rest of the time,
energy and comfort are wasted through cycling losses and poor humidity
control.
With
Airzone, a smaller HVAC unit can be used for better comfort and energy
savings. What about the 5% of hottest and coldest days? Remember, with an
Airzone System, no energy is wasted overheating and overcooling the areas
you are using, so you get more mileage from the capacity you do have.
Second, you can always setback areas not in use, and achieve total comfort
in the occupied zones.
The other
95% of the year is rewarded with significant gains in energy savings and
comfort. Call Retrozone, Inc. for more information on this subject.
B. Hot
and Cold Spots - Using multiple thermostats and multiple zones of control,
Airzone puts air exactly where it’s needed, by "borrowing" the air from
unoccupied or satisfied areas.
C. Poorly
Designed Duct Systems: Airzone can correct many duct design flaws since
Airzone forces the air to go exactly where it’s needed.
The key
to solving HVAC problems with Airzone is common sense and a thorough
understanding of how Airzone operates. For more Information on how Airzone
can be used to correct a problem duct system, call the Retrozone Factory.
Copyright RetroZone 2013
 |