SECTION 4 Airzone
Controllers - General Information
Specific information
on individual Airzone Control Systems are included with each panel,
including wiring and other information. The following information is
generic to all Airzone Systems.
The Airzone
Trouble Shooting Manual contains more information on how individual
components work.
A. Where to locate the Airzone control
panel.
B. Flexdamper actuating times.
C. Pump hook-up and other information.
D. Solenoid-Slave Zone information.
E. Thermostats
A. Where to Locate
the Airzone control panel(s)
Note: Consult
Section 6 "avoiding noise problems" as this section may impact locating
the Airzone Central Control Equipment.
If possible, the
Airzone Control Units should be mounted in a conditioned space, away from
temperature extremes. Doing so will prolong the life of all components.
However, it is
acceptable to mount Airzone Control Units in attics and other areas that
do not exceed 130ºF.
Most Control Panels
are rated for 130ºF duty, but Retrozone strongly recommends the mounting
of these panels in conditioned space. This may be useful also because of
the status LED lights, which can provide user feedback. It is acceptable
to mount the control panels remotely from the Airzone Solenoid panel.
While all Airzone
equipment should be easily accessible for service, all user inputs are
from the control panel only.
B. Flexdamper
Actuating Times - How fast is fast enough?
The speed at which
Flexdampers actuate is dependant on several factors, including:
1. The size of the
Flexdampers on each zone.
2. The length of the
tubing.
3. The timing of the
call to actuate - are other zones also calling?
95% of all new
Airzone installations operate satisfactorily on just one pump. Should the
reaction time of the Flexdampers be too slow, a second expansion pump can
easily be added later.
In most cases,
Airzone Central Control Equipment is located near the inside
furnace/blower section of the HVAC. Keep tubing lengths as short as
possible, although runs of 50 and 100 feet are common. Excessively long
tubing runs will slow Flexdamper actuating times, perhaps making a second
pump necessary.
Any application with
more than one 12 or 14 inch Flexdamper on a zone may be a candidate for a
second Airzone pump. Excessive air tubing lengths or amounts may also
slow reaction times.
C. Pump hook-up
and other information. See fig. 4-1
The Airzone pump is
a long life, continuous duty type pump.
Pumps are designed
to be powered by two 24VAC wires - one going to the HVAC transformer (as
shown in fig. 4.1) the other going to the transformer powering the
control panel (labeled "24VAC" in fig. 4.1). All pumps have an internal 24vac relay
with three connecting wires. Wire pump as described in the inside cover
panel instructions of your Airzone System.
The troubleshooting
manual contains detailed information on the pump and relay, however please
note:
* The black wire
connects to the common wire of the HVAC's 24vac Transformer, NOT the
Airzone transformer.
* The pump is
designed to hang loosely from a nail or screw, over-tightening can split
the rubber mounting tab.
* Heat Pumps often
do not require connection of both green and red pump relay wires. It is
acceptable to connect just one pump relay wire to any (24vac low voltage
only!) heat pump control wire that is energized in all modes (usually the
fan wire)
* In certain
applications it may be necessary to run the pump continuously, simply wire
the pump directly to the Airzone transformer with the common and red or
green pump relay wire.

Fig 4-1
D. Solenoid -
Slave Zone information. See Fig. 4-2
"Solenoid Air Switches"
CAUTION: Do not
remove or tamper with the pressure and vacuum relief valves installed
inside the Airzone System. These important valves must remain in the
proper lines, and pointed in the proper direction.
Any Airzone solenoid
can be changed from normally open operation to normally closed operation.
Simply disconnect and reverse the two tubing connections to each solenoid
as shown. DO NOT reverse the vacuum and pressure relief valves as severe
damage to the system can result.
“Normally open"
means that when de-energized, the solenoid air switch connects the vacuum
line of the pump to the Flexdamper, causing it to open or remain open.
"Normally Closed"
means that when de-energized, the solenoid air switch connects the
pressure line of the pump to the Flexdamper, causing it to close and
restrict air flow.
SLAVE ZONES- Slave
zones are zones where a thermostat or a switch directly controls the
solenoid/Flexdamper to simply close off airflow to an area, without
controlling the HVAC system.
Slave Zone
Thermostats - Use the normally closed solenoid configuration, since a
thermostat will energize the solenoid when airflow to an area is needed.
Toggle switch or
other slave zone control - Depending on the application, use whatever mode
- normally open or normally closed (see Fig. 4-2) - that will
result in the solenoid being energized the least amount of time.
Retrozone recommends doing so to reduce energy use and prolong component
life.
Fig 4-2
E. Thermostat
Mounting Location and other information.
Correct thermostat
mounting - Careful location of the Retrozone thermostats will have great
importance on the comfort and energy efficiency of the HVAC unit, and can
greatly reduce wiring time and costs.
Fig. 4 - 3
shows a typical floor plan of a home, divided into five zones. The
thermostat for each zone should be centrally located within each zone.
The thermostat for
each zone:
- should not be
located on an outside wall, above a lamp, in direct sunlight, in the
direct air-stream from a register, or anywhere else where a false reading
may occur.
- should be located
about 5 feet from the floor, in an area that receives good air circulation
for that zone only.
FIGURE 4 - 3
EXPLAINED: The "T" in a circle represents a thermostat.
Wiring tip Fig 4 -
3A: Whenever possible, locate the zone thermostat on a wall shared with a
closet, utility room, or other room where the thermostat wire can be run
through the wall and then up the closet (or other) wall, and through the
ceiling or floor. This wiring method is far easier than "fishing" wire
between walls.
Zone 1 thermostat
includes both the living room and dining room, and is located where the
radiant heat from the fireplace will not give the thermostat false
readings.
Zone 2 thermostat
includes the den and entrance, and is located to sample the temperature
between both. A less desirable, but easier to wire location is also
shown, since the wire can be run inside the pantry. Thermostats should
always be mounted in the middle of a zone, if possible.
Zone 3 thermostat
is mounted between the kitchen and the breakfast nook, where the
thermostat can "sample" the temperature from both areas. Also, the
thermostat is located on a pantry wall, simplifying wiring (see Fig 4 -
3a) by eliminating the need to "fish" wire between the walls.
Zone 4 thermostat
should be located in whichever bedroom is most used, or most sensitive -
such as the case of a newborn. Mounting on outside of closet simplifies
wiring (see fig 4 - 3a).

Fig 4-3
Zone 5 thermostat
- Even if this was a two zone
job (living - sleeping zone), the sleeping zone thermostat almost always
should be mounted in the master bedroom. In this example, the thermostat
is mounted in an excellent spot -
interior wall, close
to the bed, AND in an area where it can "sample" both bedroom and master
bath temperatures.
The same thermostat
location strategies apply to commercial jobs in the same manner.
SECTION 4 OUTSIDE
AIR INTAKE See Fig. 4 - 4
Forward: Often
outside air can be used to provide a "free" source of cooling and
ventilation into a home or office. In many parts of the country, the air
conditioning is forced to run to remove sun load latent heat. Sometimes
special situations dictate the need for occasional ventilation, such as
Radon concentrations. The Airzone outside air option can provide an
effective solution.
Basic outside air
control: To selectively use outside air, the normal return air must be
equipped for control by Flexdampers. In addition, a duct needs to be run
between the return air plenum and an outside air location.

Fig 4-4
Fig 4-5
The outside air
pick-up duct's (Fig. 4 - 5)
length should be as short as possible. Size the outside air pick-up duct
as large as possible. This will insure maximum effectiveness of outside
air use.
Control Sequence:
See Fig. 4 - 5
The outside air
system is provided with a manual toggle switch to, when activated, provide
the following:
a. Flexdamper(s)
actuate to block the normal return air path while another Flexdamper opens
in the outside air duct. If equipped, a vent duct would open for
discharge air.
b. The 24vac control
signal to the compressor and heat exchanger is blocked, preventing either
from running.
c. The Airzone
System remains operational, so outside air can be directed into any zone.
The ability to direct all the outside air into one zone enhances the
ventilation capabilities of the outside air system.
d. Advanced controls
are under development; consult factory for information.
Copyright RetroZone 2013
 
|