SECTION 1
The Round Flexdamper
ROUND FLEXDAMPER
ASSEMBLY INFORMATION 1290
Study all instructions
carefully before beginning. Refer to Round Flexdamper assembly diagrams
before beginning.

Round Flexdamper assembly
diagrams
Tape
Connection - On some larger
Flexdampers, it may be necessary to use two or more lengths of tape to
secure the ends together. Once installed, the duct contains the Flexdamper
and prevents the tape from pulling apart.
Try to
keep the connect tape and Flexdamper warm during assembly to aid in good
adhesion. This special tape "sets" over time and provides a strong bond.The Nylon
"T" connector taped to each Flexdamper should be removed and saved for
splicing the Flexdamper tube into other Flexdamper tubes serving the same
zone.
ROUND FLEXDAMPERS-INSTALLATION
METHODS
SECURING THE FLEXDAMPER IN HIGH VELOCITY, VERTICAL, OR OTHER DUCTS- OPTIONAL
ADHESIVE MOUNTING.
CAUTION Use only pure silicone
adhesive. Other adhesives may not meet UL or other safety requirements.
PLEASE
READ! Most Flexdampers when
used in most horizontal ducts require no adhesive. The semi-rigid internal
belt in the Flexdamper allows it to stand upright in the duct, while the
tubing should be cut to a length that keeps the Flexdamper from sliding down
the duct.
However,
certain applications exist where a more secure bond to the duct is required,
such as a vertical duct where the tubing, because of mounting needs, runs
downward and does not support the Flexdamper.
Retrozone
highly recommends the use of silicone adhesive on larger Flexdampers and
Flexdampers mounted in vertical ducts. In fact, since it is so easy to do,
Retrozone recommends the "First Stage" adhesive mounting for all Flexdampers,
to insure trouble-free operation.
Fig
1-11. Stage 1 adhesive mounting
- Optional but recommended for all Flexdampers. Install air tubing on
Flexdamper. Then place a liberal amount of silicone adhesive on the top,
center taped joint of the Flexdamper. Install in duct.
Fig.
1-12 Stage 2 adhesive mounting -
recommended for vertical, high velocity and other special applications. Add
two, 2 inch strips of connect tape to outside area of Flexdampers, centered
between divider seals. Apply adhesive to tape strips. Apply silicone
adhesive to top tape joint (same as
Fig.1-11).
Install
Flexdamper in duct. Inflate Flexdamper orally or with the Airzone Panel (Fig
1-13) to allow the silicone to
cure. Flexdamper should now be supported by adhesive in two places evenly
spaced around Flexdamper.

Fig 1-11,1-12,and 1-13
Fig.1-16 In-line installation.
Useful in many applications using steel or rigid duct, including Northern
homes where ducts are run under floor joists.
Carefully
peel back insulation, uncovering a suitable amount of duct. Drill a 3/8”
hole to enable the use of tin snips. (You may want to drill a second 3/8”
hole about 18 inches upstream, if the air tube is to exit the duct).
Then,
using tin snips, cut out a three-sided "half moon" piece of sheet metal
large enough to easily fit one's hand and a rolled Flexdamper through. The
larger the duct, the larger the Flexdamper, so the larger the hole should
be.
Bend back
the sheet metal on the uncut axis. Now, work through this opening to
install the Flexdamper. The Flexdamper may be tightly rolled to a small
diameter, but try not to crease the internal belt.
Caution!
Wear gloves and long sleeves, and avoid snagging either yourself or the
Flexdamper on the sharp sheet metal edges.
Hint:
You may find it easier to attach the connect tubing to the Flexdamper before
you insert it through the hole. If using optional silicone adhesive, try
putting the adhesive on after the Flexdamper is in the duct.
After
installation is complete, bend sheet metal back in place, and tape or caulk
to insure an airtight seal. Tape insulation back in place.

Fig 1-16
Fig.
1-17 Splitter installation - In
many installations, one large (trunk) duct will
split
into two or more smaller (branch) ducts. If the smaller ducts branching
from the larger duct serve the same zone, then only one Flexdamper in the
larger duct is needed.
However,
if the branch ducts serve different zones, then a Flexdamper will need to be
installed in each of these branch ducts.
Many
different types of duct "splitters" exist- sheet metal, fiberboard, etc.
Similar
to a plenum installation, often one duct can be removed to allow
installation in the other ducts branching from the splitter. Transitioning
the air tubing from the Flexdampers through holes drilled in the splitter is
often convenient.
Fig. 1-18 Register Installation - The register installation is often a good choice,
since the Flexdamper can be installed by simply removing the register. Read
Section 6 on avoiding noise problems for register installations.
Working
up through the register, first size the Flexdamper to the correct diameter
(see Fig. 1-8). Since many register installations are in vertical duct,
review adhesive mounting methods
(Figs. 1-11 to 1-13)
Next,
drill a 3/8” hole in the duct at least a foot or more upstream of where the
Flexdamper will be located (not necessary if tube is to run inside of duct
back to plenum). With flexible type duct, reinforce both inner and outer
membranes with connect tape before punching hole. Working from above the
ceiling, run a length of tubing into duct and out through register.
Make sure
area where Flexdamper will be mounted is free of sheet metal screws. Attach
end of air tube to the Flexdamper, apply silicone adhesive if applicable,
then insert and install in duct.
Fig.
1-13 For all Flexdampers using
silicone adhesive, especially vertical mounts:
If
possible, immediately after installation inflate Flexdamper orally or with
Airzone Control System and leave inflated (plug tube) for as long as
possible to insure a good bond.
Caution:
Do not use compressed air or any source over 3 PSI.

Fig 1-11 to 1-13
HELPFUL HINT- Install
Flexdampers needing adhesive mounting first to allow more curing time on the
adhesive.
Fig.1-11 The tubing should be
cut to a length that limits the Flexdamper from sliding down the duct. When
doing a register or in line duct Installation, leave enough tubing upstream
to move through an up and down arc as the Flexdamper inflates and deflates.
INSTALLING THE
FLEXDAMPER
Study the
"FLEXDAMPER INSTALLATION DIAGRAM" (Fig
1-15) carefully before
attempting installation. Different methods of installation exist to install
the Flexdamper, depending on the application.
General Notes, all Round Flexdampers:
The air
tubing used with the energy saving Airzone System is very durable, but
somewhat stiff. When installing a Flexdamper, straighten the air tube or
locate the Flexdamper in such a way that the air tube is not "fighting" the
Flexdamper.
Round
Flexdampers work great in steel or flexible duct. Whenever transitioning a
tube through flexible duct, reinforce the inside membrane with a patch of
connect tape before punching hole.
Fig.
1-15 Plenum Installation -
Note: This type of installation is recommended for new construction
applications. Design the plenum so that all Flexdampers can be installed
and serviced through an access door installed in the plenum.
Retrofit
Plenum Installation: Particularly useful in southern applications where
ducts are often "homerun" to the plenum, installing the Flexdampers from
inside the plenum can be fast and easy. Should not enough room exist for an
access door (or the distance from the access door to a duct(s) is too far),
you may be able to remove just one (preferably larger) duct, and gain access
to the inside of the plenum in this manner.
CAUTION! Be sure not to mount
Flexdampers over sheet metal screws that are sometimes present in plenum
starting collars. While incredibly tough, the Flexdamper over time may
develop a leak, which can diminish system performance.
Fig.
1-15a. Flexdampers installed
from the plenum and serving the same zone can be connected together inside
the plenum, so that only one tube for each zone needs to be run through the
plenum and to the energy saving Airzone System. Make sure Flexdampers don't
have enough tubing to slide down the duct.
Fig.
1-15b Drill a 3/8” hole in the
plenum for each zone tube that needs to transition through the plenum.
Fig.
1-15c Plenum access door
installed on plenum.

Fig 1-15
CAUTION! Especially when new,
round Flexdampers can make a "popping" noise when inflating. Locating the
Flexdamper at the register, especially in steel duct, may cause a slight but
objectionable noise in a bedroom area. However, this typically is only a
problem if the Flexdampers are moving during the night: In homes where the
sleeping area is one zone, and where the other zones will be set back at
night, the Flexdampers will seldom actuate. Avoid placing the Flexdamper at
the register in a bedroom if you anticipate the Flexdamper repeatedly
changing positions during the night.
Fig 1-16

Fig 1-17
Copyright RetroZone 2013
 
|