RZ135-7
Installation Instructions
Connecting RZ135-7 Motor to Zone Panel with Only 2 Wire Damper Outputs (this includes many ZTech, Jackson, Aprilaire, Lennox, and other new construction-type panels) or Connecting Thermostat directly to RZ135-7 Motor.
1. Turn all thermostats to "off".
2. From motor to panel:
A. Connect RZ135-1 white wire to M1 or COMMON to RZ135-7 white wire;
B. Connect RZ135-7 green wire to any thermostat input "R" on board (but NOT to "R" on equipment outputs nor the 24VAC transformer input); and
C. Connect RZ135-7 red wire to M6 or NORMALLY CLOSED (NC) or POWER TO OPEN.
4. With all thermostats turned off and the HVAC system at rest, go ahead and power up the motor BEFORE mounting it on the damper. This will rotate the damper to the open position (or, it should). Then mount the damper with the blade in the open position and you should be ready to test operation. If it is operating backwards, just reverse the green and red wire.
Remember: Travel time is 15-30 seconds for 90° on a round damper and 30-60 seconds for 180° on a rectangular damper. Watch damper shaft closely to ensure movement.
Notes: All modern zone control panels open the dampers at the end of each cycle. Dampers should open when there is no call for heat or air, i.e., the system is at rest. If the motor closed the damper when the system is at rest, switch the red and green wires which should cause damper to open.
* A good test is to turn all thermostats to "off" position and insure all dampers are open if not, switch the red and green wires to cause dampers to open.
What's going on:
If you have a volt meter, you can check this - Here is what you are trying to do:
⚫ 24vac power is being applied full time to motor white and green wires.
Green = Any
thermostat input "R"
on board
Do not connect
to "R" in
Equipment
Outputs nor 24
vac Transformer Input!
24vac
Transformer
Input
2
Damper
Output
Per ZoneThermostat
Inputs
Equipment
Outputs
Thermostat
Inputs
White = 24V COMMON
(M1 or Com)
Red = 24V CLOSED
(M6 or NC)